Multi-functional Automatic Generator Engine Control Module Controller
0.5 second after the fuel relay is energised, the 3 attempt start will begin its start sequence: the start relay will energise, feeding battery +ve on terminal 7 to terminal 2 and thence on to the start circuit. The crank period is set for 12 seconds (this time is auto-regulated and may be shorter). If the engine has not fired by the end of 1st attempt, the starter is turned off for a 20 sec. period. The sequence will then repeat up to a maximum number of start attempts. Following a successful start, sensed when AC alternator's frequency rises above 30Hz, the crank relay is de-energised and latched out to prevent re-engagement of the starter with the engine running. When 10 second pre-heating cycle is timed out and flashing LED on the module is turned off, the module will begin its start.